– 3 –
MODEL RAS-13UKHP-E4 / RAS-13UAH-E 4 RAS-13UKP-E4 / RAS-13UA-E4
ITEM Cooling Heating Cooling
Capacity 
220 V  240 V  220 V  240 V  220 V  240 V
kW 3.55 3.60 4.10 4.15 3.70 3.75
Phase  1Æ
Power source  V  220 - 240
Hz 50
Power consumption kW 1.23 1.27 1.26 1.33 1.24 1.28
Power factor % 99 97 98 96 98 95
Running Indoor A 0.15
current Outdoor A 5.50 5.30 5.35 5.15 5.75 5.60
Starting current A 25 24
Moisture removal lit/h 2.0
Noise
Indoor (H/M/L) dB 41/35/31
Outdoor (220 - 240 V) dB 49 51 49 51 47 48
Refrigerant
Name of refrigerant R22
Rated amount  kg  1.00  0.80
Refrigerant control Capillary tube
Gas side size  mm  Æ12.7
Connection type Flare connection
Liquid side size  mm  Æ6.35
Interconnection
Connection type Flare connection
pipe
Maximum length
1
(One way)
Maximum height
difference
INDOOR UNIT RAS-13UKHP-E4 RAS-13UKP-E4
Height mm 275
Dimensions  Width  mm  790
Depth mm 208
Net weight  kg  10
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m
3
/h 630 650 630
Air volume Medium fan m
3
/h 520 550 520
Low fan m
3
/h 430 490 430
Fan motor output W 20
Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-13UAH-E4 RAS-13UA-E4
Height mm 550
Dimensions Width mm 780
Depth mm 270
Net weight kg 37 34
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume  m
3
/h  2120 
2200 
2120  2200  2030  2150
Fan motor output W
42
Compressor
Model  
PH225X2C-4FT
Output  W 1100
Safety device Fuse, Overload relay
Louver type Automatic louver
Usable outdoor temperature range °C 15 ~ 43 -10 ~ 24 15 ~ 43
1. SPECIFICATIONS
   m
  m
 6
30
 15*
FILE NO. SVM-05001