7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 077SKV-E5 0.9 to 1.1 9 to 11 47 to 49 High High 50
107SKV -E5 0.9 to 1.1 9 to 11 47 to 49 High High 73
137SKV -E5 0.8 to 1.0 11 to 13 46 to 48 High High 94
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 077SKV-E5 2.4 to 2.6 43 to 45 0 to 3 High High 60
107SKV -E5 2.4 to 2.6 43 to 45 0 to 3 High High 94
137SKV -E5 2.6 to 2.8 41 to 43 0 to 2 High High 94
condition(°C)
Tempeature Heat exchanger
pipe temp.