7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/-
10N3KV2-A
0.9 to 1.1 12 to 14 37 to 39 High High 49
13N3KV2-A
0.8 to 1.0 11 to 13 46 to 48 High High 59
16N3KV2-A
0.8 to 1.0 11 to 13 40 to 42 High High 67
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 10N3KV2-A 2.5 to 2.7 39 to 41 0 to 3 High High 60
13N3KV2-A 2.6 to 2.8 41 to 43 0 to 2 High High 66
16N3KV2-A 2.7 to 2.9 43 to 45 0 to 2 High High 67
condition(°C)
Tempeature Heat exchanger
pipe temp.