– 10 –
5. REFRIGERANT CYCLE DIAGRAM
RAS-13SK-E / RAS-13SA-E
RAS-13SKX / RAS-13SAX
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Fig. 5-1
Table 5-1
Evaporator
Indoor unit
Cross flow fan
Compressor
Accumulator
Condenser
Propeller fan
Outdoor unit
Dryer
Capillary tube
ø1.7 x 900
PH160T2-4L2
Mark ( ) means check points of Gas Leak
Auxiliary pipe
0.49m
ø6.35 (ø1/4 in)
T1
P
Refrigerant
R22 0.83kg
Connecting pipe
ø6.35 (O.D.)
(ø1/4 in)
Auxiliary pipe
0.39m
ø9.52 (ø3/8 in)
Connecting pipe
ø12.7 (O.D.)
(ø1/2 in)
Max. longth 15m
Allowable height 6m
Cooling
50Hz
Standard
Cooling High temperature
Low temperature
Standard pressure
P
(kg/cm²G)
13SK-E
13SKX
5.0
6.0
3.0
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
13SK-E
13SKX
10.0
15.0
2.0
Fan speed
(indoor)
High
High
Low
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
27/19 35/24
32/23 43/26
21/15 21/15