– 9 –
4. SPECIFICATIONS OF ELECTRICAL PARTS
4-1. Indoor Unit
RAS-13SK-E
RAS-13SKX
4-2. Outdoor Unit
RAS-13SA-E
RAS-13SAX
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Parts name
Fan motor (for indoor)
Thermo sensor
(TA-sensor)
DC-DC transformer (T01)
Microcomputer
Power relay (RY01),
Common relay (RY02)
Heat exchanger sensor
(TC-sensor)
Line filter (L01)
Diode (DB01)
Capacitor (C02)
Fuse (F01)
Power supply IC (IC01)
Varistor (R21, R109)
Resistor (R01)
Louver motor
Type
ICF-35-19-3
or
TICF-35-19-3
(microprocessor)
SWT-34
TMP87CK40F
DI1U
(microprocessor)
RF-103YOR6
RBV-406
CEAUF2W101M20
MT3
MA2830-FJ
15G561K
ERF-5TK5R6
MP35EA7
Specifications
DC35V, 19W
10k at 25°C
DC390V, Secondary DC35V, 12V, 7V
Coil : DC12V 75mA, Rated AC250V 20A
10k at 25°C
10mH, AC 0.6A
4A, 600V
100µF, 450V
T3.15A, 250V
4A, 600V
560V
5.6 , 5W
Output (Rated) 2W, 10poles, 1phase, DC12V
No.
1
2
3
4
5
Parts name
Compressor
Fan motor (for outdoor)
Running capacitor
(for fan motor)
Running capacitor
(for compressor)
Overload relay
Type
PH160T2-4L2
UE6-31C5P
SK-50FMP
SK-40CMP35U1
J-MRA99253-9200
Specifications
Output (Rated) 1100W, 2pole, 1phase, 220/230/240V, 50Hz
Winding resistance ()
(at 20°C)
Output (Rated) 27W, 6pole, 1phase, 220/230/240V, 50Hz
Winding resistance ()
(at 20°C)
500V AC, 1.5µF
400V AC, 35µF
U/T 10.1A (80°C), OPEN 135±5°C, CLOSE 75±11°C
Red-Black White-Black
2.38 3.65
Red-Black White-Black
210 435

Table of Contents