7-7. Current Limit Control
The microprocessor detects the input current so as to
prevent it exceeds a specified value by means of
controlling the outdoor fan control as described in (1)
and (2).
(1) Current limit control (Cooling)
Control is performed as shown below by detecting
the compressor operating current with a current
sensor (C.T).
RAS-13UKHP-E / RAS-10UKHP-E / RAS-07UKHP-E
(2) Current limit control (Heating)
Control is performed as shown in Fig. 7-7-2
RAS-13UKHP-E / RAS-10UKHP-E / RAS-07UKHP-E
Remark :
This function is available only for heat pump model
(Cooling models have no a current sensor (C.T.)).
Input current
13.5A/ 19.2A I4
12.5A/ 17.8A I3
Compressor Outdoor fan
More than I
4 continues for 3 seconds
OFF
More than I
3 continues for 5 seconds
OFF
ON
Input current
13.5A/ 19.2A I4
12.5A/ 17.8A I3
10A/ 15.6A I2
9A/ 15.0A I1
Compressor Outdoor fan
More than I
4 continues for 3 seconds
OFF
More than I
3 continues for 5 seconds
OFF
ON
ON OFF