– 33 –
FILE NO. SVM-02001
8-2. Installation Diagram of Indoor and Outdoor Units
For installation of the indoor unit, use the paper pattern on the back of the installation manual.
Before installing the wireless
remote control
• With the remote control cover
open, load the batteries supplied
correctly, observing their
polarity.
2 Wireless remote control
Cover
Shield
pipe
Air filter
Be sure to use the
Electric parts cover
Hook
(Attach to the front panel)
2 Wireless remote
control
65 mm or more
170 mm
or more
600 mm or more
B mm or more
A mm or more
Loop the connective cable
(about 100 mm in diameter
and 300 – 350 mm long).
8 Pan head wood screw
6 Purifying filter
5 Zeo lite filter
4 Remote control holder
Vinyl tape
Apply after
carrying out a
drainage test.
Saddle
A
B
07, 10 class
400 mm
45 mm
(10-13 Class)(07 Class)
600 mm or more
B mm or more
100 mm or more
A mm or more
600 mm or more
Vinyl tape
Apply after
carrying out a
drainage test.
Saddle
Extension
drain hose
(Option:
RB–821SW)
Hook
170 mm
or more
Wall
Insert the cushion between
the indoor unit and wall,
and tilt the indoor unit for better
operation.
The auxiliary piping can be
connected the left, rear left,
rear right, right, bottom right or
bottom left.
Left
Rear left
Right
Rear right
Bottom right
Bottom left
Insulate the refrigerant pipes
separately with insulation, not
together.
6 mm thick heat resisting
polyethylene foam
Do not allow the drain hose to
get slack.
Make sure to run the drain hose
sloped downward.
Cut the piping hole
sloped slightly
For the rear left and left piping
600 mm or more
Extension
drain hose
(Option:
RB–821SW)
1 Installation
plate
13 class
600 mm
100 mm
2 Batteries
100 mm or more