FILE NO. SVM-03004(1)
5-3. RAS-13UKP-E2 / RAS-13UA-E2
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.48 9.0 High 27/19 35/24
Cooling Overload 0.59 15.0 High 32/23 43/26
Low temperature 0.45 2.0 Low 21/15 21/15
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
50Hz
Heat exchanger
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
Capillary tube
1.7 x 1000s
PH160T2-4LH2
Cooling
Mark ( ) means check points of Gas Leak.
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Packed valve
(12.7)
Packed valve
(6.35)
0.39 m
(Connecting pipe)
12.7
0.49 m
(Connecting pipe)
6.35
T1
P
Refrigerant
R22 : 0.80 kg.