– 29 –
8-1-4. Prevent-freezing control
The indoor heat exchanger sensor detects refrigerant
vapor temperature in COOL/DRY operation. If the
temperature is below the specified value, compressor
motor speed is reduced so that operation is performed
in temperature below the specified value to prevent-
freezing of indoor heat exchanger.
8-1-5. P.M.V. (Pulse Modulating Valve)
Using P.M.V., refrigerant flow of refrigeration cycle is
varied for the optimum temperature.
After the power has been turned on, when a serial
operation signal is received from indoor at the first
time, or when PMV alarm is detected and the equip-
ment is reactivated, move the valve once until it hits on
the stopper for positioning of the valve. In this case,
ticktack sound may be heard.
8-1-6. Louver control
(1) Vertical air flow louvers
Positions of vertical air flow louvers are
automatically controlled according to the operation
status (AUTO (A), COOL ( ), DRY (
), HEAT( )
and FAN ONLY (
). Besides, positions of vertical
(2) Swing
If the [SWING] button is pressed during running
operation, vertical air flow louvers start swinging.
When the [
SWING] button is pushed, swinging stops.
8-1.7. Indoor fan control
(1) The indoor fan is operated by the stepless speed
change
motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
+
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
LOW
+
=
MED
+
=
LOW+MED
2
MED+HIGH
2
air flow louvers can be arbitrarily set by pushing the
[FIX] button.
Table 8-1-2
Operation Fan
mode mode Remote Speed Air flow Speed Air flow
Control (rpm)
(m
3
/h)
(rpm)
(m
3
/h)
H HIGH 1210 590 1560 760
M+ 1130 530 1430 700
MED+ 1110 520 1440 710
Cooling and M MED 1010 460 1330 640
Fan only LOW+ 910 410 1230 600
L+ 880 390 1230 600
L LOW 810 350 1130 530
L- 780 330 1030 470
L+ 880 390 1230 600
L 810 350 1130 530
Dry L- 780 330 1030 470
UL 720 290 920 410
SUL 660 260 860 380
H HIGH 1290 620 1600 780
M+ 1290 620 1560 760
MED+ 1200 570 1510 740
M MED 1110 520 1430 700
Heating LOW+ 1020 470 1330 640
L+ 1010 460 1330 640
L LOW 930 420 1230 600
L- 880 390 1230 600
UL 780 330 1030 470
SUL 550 180 750 310
13NKV 16NKV