21
FILE NO. SVM-04008
Evaporator
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PH250X3-4LM
Accumulator
Cooling
Heating
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Heating
Gas container connection (Reinstall etc.)
Packed valve
(
6.35)
Packed valve
(
12.7)
0.49 m
(Connecting pipe)
12.7
0.39 m
(Connecting pipe)
6.35
T
P
Refrigerant
R22 1.29 kg
Mark ( ) means check points of Gas Leak
Capillary tube
0.8x500 s
Capillary tube
1.2x1500 s
Capillary tube
2.0x1200 s
5-2. RAS-18UKHP-E3 / RAS-18UAH-E3
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.4 45.0 High 20/ 7/6
Heating High temperature*1 0.5 ~ 0.6 49.0 ~ 58.0 Low 27/ 24/18
Low temperature 0.3 34.0 High 20/––10/10
Standard 0.4 10.0 High 27/19 35/24
Cooling High temperature 0.5 15.0 High 32/23 43/26
Low temperature 0.3 1.0 Low 21/15 21/15
Fan speed
(indoor)
50 Hz
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)