5-3. RAS-18UK-AR / RAS-18UA-AR
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Indoor unit
Cross flow fan
Compressor
Condenser
Propeller fan
Outdoor unit
PH250X3-4LM
O.D.:12.7mm O.D.:6.35mm
Packed valve
( 12.7)
Packed valve
( 6.35)
T
P
Refrigerant
R-22 1.17 kg
Evaporator
Capillary tube
2.0x1000
S
0.39m
(Connecting pipe)
12.7
0.49m
(Connecting pipe)
6.35
Capillary tube
0.8x900
S
Mark ( ) means check points of Gas Leak
Cooling
Standard 0.4 10.0 High 27/19 35/24
High temperature 0.6 13.0 High 32/23 52/31
Low temperature 0.3 2.0 Low 21/15 21/15
50Hz
Fan Speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard
Pressure
PP
PP
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
TT
TT
T (°C)