– 37 –
Item Operation flow and applicable data, etc. Description
2. Indoor fan
motor
control
3) In heating operation, the mode changes to [LL] if thermostat is
turned off.
4) If Ta ≥ 25°C when heating operation has started and when defrost
operation has been cleared, the air conditioner operates with (H)
mode or higher mode for 1 minute after Tc entered in E zone of cool
air discharge preventive control.
5) Self-clean operation
When performing self-clean operation after stopping the cooling
operation, the mode becomes 610 rpm (M07, 10, 13, 24 type), 630
rpm (M16, 22 type).
[Self-clean ] is displayed.
tap COOL HEAT
External static pressure selection
10Pa 20Pa 35Pa 45Pa
F1 HH 1080 1140 1240 1280
F2 HH 1080 1140 1240 1280
F3 H+ 1020 1080 1180 1220
F4 H+ 1020 1080 1180 1220
F5 H 950 1020 1100 1160
F6 H 950 1020 1100 1160
F7 L+ 890 960 1040 1100
F8 L+ 890 960 1040 1100
F9 L 830 890 970 1020
FA L 830 890 970 1020
FB L- 690 720 760 790
FC L- 690 720 760 790
FD LL LL 550 550 550 550
■
22 type
tap COOL HEAT
External static pressure selection
10Pa 20Pa 35Pa 45Pa
F1 HH 1120 1180 1280 1300
F2 HH 1120 1180 1280 1300
F3 H+ 1060 1120 1200 1260
F4 H+ 1060 1120 1200 1260
F5 H 980 1040 1120 1180
F6 H 980 1040 1120 1180
F7 L+ 920 980 1060 1100
F8 L+ 920 980 1060 1100
F9 L 840 900 980 1020
FA L 840 900 980 1020
FB 700 730 770 790
FC 700 730 770 790
FD LL LL 550 550 550 610
■
24 type