– 21 –
1-3. Electrical Data
Outdoor Unit : RAS-4M27YAV-E
<Cooling>
System Compressor Fan motor FLA
Voltage range Power supply
Combination of
indoor unit operation
Hz
Volts-
Ph.
Min. Max. MCA ICF
MOCP
(Amps)
MSC RLA Indoor Outdoor
10 ––– 4.48 4.48 20 3.06 3.06 0.15 x 1 = 0.15 0.5
13 ––– 6.70 6.70 20 4.84 4.84 0.15 x 1 = 0.15 0.5
1 unit
16 ––– 9.18 9.18 20 6.82 6.82 0.15 x 1 = 0.15 0.5
10 10 –– 8.29 8.29 20 5.99 5.99 0.15 x 2 = 0.30 0.5
13 10 –– 9.84 9.84 20 7.23 7.23 0.15 x 2 = 0.30 0.5
16 10 –– 11.11 11.11 20 8.25 8.25 0.15 x 2 = 0.30 0.5
13 13 –– 11.11 11.11 20 8.25 8.25 0.15 x 2 = 0.30 0.5
16 13 –– 12.66 12.66 20 9.49 9.49 0.15 x 2 = 0.30 0.5
2 units
16 16 –– 13.94 13.94 20 10.51 10.51 0.15 x 2 = 0.30 0.5
10 10 10 – 13.08 13.08 20 9.70 9.70 0.15 x 3 = 0.45 0.5
13 10 10 – 13.13 13.13 20 9.74 9.74 0.15 x 3 = 0.45 0.5
16 10 10 – 13.13 13.13 20 9.74 9.74 0.15 x 3 = 0.45 0.5
13 13 10 – 13.13 13.13 20 9.74 9.74 0.15 x 3 = 0.45 0.5
16 13 10 – 13.24 13.24 20 9.83 9.83 0.15 x 3 = 0.45 0.5
13 13 13 – 13.24 13.24 20 9.83 9.83 0.15 x 3 = 0.45 0.5
16 16 10 – 13.30 13.30 20 9.88 9.88 0.15 x 3 = 0.45 0.5
16 13 13 – 13.30 13.30 20 9.88 9.88 0.15 x 3 = 0.45 0.5
16 16 13 – 13.30 13.30 20 9.88 9.88 0.15 x 3 = 0.45 0.5
3 units
16 16 16 – 13.35 13.35 20 9.92 9.92 0.15 x 3 = 0.45 0.5
10 10 10 10 13.31 13.31 20 9.77 9.77 0.15 x 4 = 0.60 0.5
13 10 10 10 13.31 13.31 20 9.77 9.77 0.15 x 4 = 0.60 0.5
16 10 10 10 13.59 13.59 20 9.99 9.99 0.15 x 4 = 0.60 0.5
13 13 10 10 13.59 13.59 20 9.99 9.99 0.15 x 4 = 0.60 0.5
16 13 10 10 13.59 13.59 20 9.99 9.99 0.15 x 4 = 0.60 0.5
13 13 13 10 13.59 13.59 20 9.99 9.99 0.15 x 4 = 0.60 0.5
16 13 13 10 13.59 13.59 20 9.99 9.99 0.15 x 4 = 0.60 0.5
13 13 13 13 13.59 13.59 20 9.99 9.99 0.15 x 4 = 0.60 0.5
4 units
16 16 10 10
50 or 60 230–1198 264
13.59 13.59 20 9.99 9.99 0.15 x 4 = 0.60 0.5
NOTE :
Model of Indoor unit 10 : RAS-M10YKV-E, 13 : RAS-M13YKV-E, 16 : RAS-M16YKV-E
MCA : Minimum Circuit Amps.
ICF : Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)
MOCP: Maximum Overcurrent Protection (Fuse only)
MSC : Maximum Starting Current
FLA : Full Load Amps.
RLA : Rated Load Amps. RLA under conditions on the right.
DB WB
Indoor temp. (°C) 27 19
Outdoor temp. (°C) 35 —