[P19 trouble]
Refer to the service manual of the outdoor unit.
Is operation of 4-way valve normal?
(Check the pipe temp., etc.
during cooling/heating operation.
Replace outdoor temperature sensors.
TE sensor
TS sensor
Indoor TC sensor
YES
NO
[F02 trouble]
Correct connection of connector.
Are characteristics of
TC sensor resistance value normal?
Is connection of TC sensor connector
(CN101 on Indoor P.C. board) correct?
Refer to TC Characteristics.
Replace TC sensor.
Replace indoor P.C. board (MCC-1643).
Correct connection of connector.
Are characteristics of
TCJ sensor resistance value normal?
Is connection of TCJ sensor connector
(CN102 on Indoor P.C. board) correct?
Refer to TCJ sensor
(Temperature-Resistance value characteristic table)
Replace TCJ sensor.
Replace indoor P.C. board (MCC-1643).
YES
YES
YES
YES
NO
NO
NO
NO
[F01 trouble]