10-3. Address Setup (Manual Setting from Remote Controller)
(Example of 2-lines wiring)
(Solid line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by 
connecting singly the wired remote controller 
without remote controller inter-unit wire.
Outdoor
Indoor
AB
AB
123
Indoor
AB
123
Indoor
AB
123
Indoor
AB
123
123
Outdoor
123
Remote controller
Line address → 1
Indoor unit address → 1
Group address → 1
1
2
2
2
1
2
2
2
2
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
Indoor unit
address
Group 
address
CODE No.
(DN)
Item
13
14
Description
0001: No.1  to  0128: No.128 … TU2C-Link
0001: No.1  to  0030: No.30 … TCC-Link
12 Line address
0001: No.1  to  0128: No.128 … TU2C-Link
0001: No.1  to  0030: No.30 … TCC-Link
0000: Individual
0001: Header unit
0002: Follower unit
<RBC-ASCU1
∗∗
∗∗
∗
>
1 Push and hold the [menu +   ] buttons at same time for more than 10 seconds.
2 Push the [OFF timer] button to confirm the selected indoor unit.
<Line address>
3 Push the [menu] button until the CODE No. flashes. And using the [   or  ] buttons,
specify the CODE No.12.
4 Push the [menu] button until the SET DATA flashes. And using the [   or  ] buttons, set
a system address.
5 Push the [OFF timer] button to confirm the SET DATA.
2
3,4
3,4
3,4
6
2,5