6. External view of P.C. board assembly
7. Address setup
In addition to set up the central control address, it is necessary to change the indoor unit number.
(Line/Indoor/Group address). For details, refer to 1:1 model connection interface Installation Manual.
9-3. How to Set up Central Control Address Number
When connecting the indoor unit to the central control remote controller using 1:1 model connection interface, it
is necessary to set up the central control address number.
The central control address number is displayed as the line No. of the central control remote controller.
How to set up from indoor unit side by remote controller
<Procedure> Perform setup while the unit stops.
Terminator (SW01)
52
85
Set the following DN with the wired remote controller
CODE No.
(DN)
Irem Description
* Refer to 8-1-4. Function Selection Setup for how to operate the remote controller.
03 Central contol address No.
0001: No.1 to 0128: No.128
࣭࣭࣭
TU2C-Link
0001: No.1 to 0164: No.64
࣭࣭࣭
TCC-Link
00Un, 0099: Unset (Factry default)
- 92 -