7-2-4. Diagnostic Procedure for Each Check Code (Indoor Unit)
Check code
[E01 trouble]
Is inter-unit cable of A and B normal?
Is group control operation?
Is power of all indoor units turned on?
Is power supplied to remote controller?
AB terminal: Approx. DC18V
Are 2 remote controllers set
without header unit?
Are 2 header units set in
2 remote controllers?
Is there no disconnection or
contact trouble of connector on harness
from terminal block of indoor unit?
Check power connection of indoor unit.
(Turn on power again.)
Check indoor P.C. board (MCC-1643).
Defect → Replace
Check remote controller P.C. board.
Defect → Replace
Correct as a header unit
and a follower unit.
Check remote controller P.C. board.
Defect → Replace
Correct a header unit/a follower unit.
(Remote controller address connector)
Correct connection of connector.
Check circuit wiring.
Correct inter-unit cab
le
of remote controller
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
[E09 trouble]