– 70 –
Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN Item Description At shipment
01
Filter display delay timer 0000: None
0002: 2500H
0004: 10000H
0001: 150H
0003: 5000H
0002 : 2500H
02
Dirty state of filter 0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
1E
Temp difference of
[AUTO] mode selection
COOL → HEAT,
HEAT → COOL
0000: 0 deg
(For setup temperature, reversal of COOL / HEAT by } (Data value) / 2)
0010: 10 degto 0003: 3 deg
(Ts ±1.5)
06
Heating temp shift 0000: 0 °C
0002: +2 °C
0001: +1 °C
0010: +10 °C
(Up to +6 recommended)
to
0002 : +2°C
2E
HA terminal (CN61)
select
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control 0000: Usual
(HA terminal)
2A
Selection of option/Trouble
input (TCB-PCUC1E-1: CN3)
0000: Filter input
0002: None
0001: Alarm input (Air washer, etc.) 0002: None
28
Automatic restart of
power failure
0000: None 0001: Restart 0000: None
14
Group address 0000: Individual
0002: Follower unit of group
0001: Header unit of group 0099: Unfixed
19
Louver type
(Air direction adjustment)
0000: No louver
0004: (4-way Air Discharge Cassette type)
0001: Swing only 0004: (4-way Air
Discharge Cassette
type)
11
Indoor unit capacity 0000: Unfixed 0001 to 0034 According to capacity
type
12 Line address 0001: No.1 unit 0030: No.30 unitto 0099: Unfixed
32 TA sensor selection 0000: Body TA sensor 0001: Remote controller sensor 0000: Body TA sensor
33 Temperature unit select 0000: °C (at factory shipment) 0001: °F 0000: °C
31 Ventilating fan control 0000: Unavailable 0001: Available 0000: Unavailable
B3 Soft cooling 0000: Unavailable 0001: Available 0001: Available
77 Dual set point 0000: Unavailable 0002: Available 0000: Unavailable
13 Indoor unit address 0001: No.1 unit 0064: No.64 unitto 0099: Unfixed
Type10
0014 : Compact 4-way Cassette 0014 : Compact
4-way Cassette
0F
Cooling only 0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0000: Heat pump
0d
Existence of [AUTO]
mode
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0001: Not provided
04
Specific indoor unit
priority
0000: No priority 0001: Priority 0000: No priority
03
Central control address 0001: No.1 unit
0099: Unfixed
0064: No.64 unitto 0099: Unfixed
60
Timer setting
(wired remote controller)
0000: Available (can be performed) 0001: Unavailable
(cannot be performed)
0000: Available
B5
Occupancy sensor/
Wireless A-B selection
Provided/None
0000: None
0002: Wireless remote controller provided
0001: Occupancy sensor provided 0000: None
B6
Occupancy sensor
Enable/Invalid
(Absence time judgment
time)
0000: Invalid
0002: 60min.
0005; 150min.
0001: 30min.
0004; 120min.
0002: Enable
(60 min.)
5d
High-ceiling adjustment
(Air flow selection)
0000: Standard
SET
DATA
Type SM40, 45SM30 SM56
0000 Standard (factory default) 2.7 m or less 2.9 m or less 3.2 m or less
0001 High-ceiling (1) — 3.2 m or less 3.4 m or less
0003 High-ceiling (3) — 3.5 m or less 3.5 m or less