Loading...
Quick Reference Guide
To assist service engineers working on Toshiba air conditioning equipment, there is a large quantity of
data available via the standard remote controller, either the RBC-AMT32E or the RBC-AMS41E, this
data is NOT available via an Infra Red remote or the RBC-AS21E2 simplified remote controller.
Accessing the data is a simple process of pressing a sequence of buttons on the remote controller.
Fault Code Guide
Current fault codes are displayed automatically on the left
of the remote controller, (Four figure display in Black) fault
code history can be accessed by pressing “Test and Set”
(The two yellow buttons) together and holding for 4
seconds.
Each controller will hold four fault codes per unit
controlled, the first displayed fault code is the youngest
and the fourth will be the oldest.
To scroll through the faults use the TEMP” buttons.
Refer to the Technical Handbook for fault code diagnosis and descriptions
Data Retrieval Guide
System data can be obtained by pressing Test and CL
together and holding for 4 seconds
Codes are displayed on the right of the remote display
To scroll through the codes use the “TEMP buttons.
Data is displayed on the left of the remote controller.
Data is available for “0, 1, 2, 3 & 4 Series” Digital/Super Digital
Inverter and VRF equipment (SMMS, SHRM & SMMSI).

Other manuals for Toshiba RBC-AMS41E