Programming
□ Verify the basic parameters and record new values of any changed parameters
Recommended Carrier Frequency is 4.0kHz. Change f701 before thr to avoid dealing with percentages.
Motor kW and RPM are not necessary to enter in the drive unless performing an auto-tune. Refer to S15 App
Note 2.8.0 Motor Auto-tuning.
STEP
B
Startup Parameters
Parameter Description Default Value New Value
aul
Overload Characteristic Selection 1
cmod
Command Mode Selection
(Start/Stop Command)
1: Panel Keypad
fmod
Frequency Setting Mode Selection 1
(Frequency Reference)
0: Setting dial 1
acc
Acceleration Time 1 10.0 s
dec
Deceleration Time 1 10.0 s
fh
Maximum Frequency 80.0 Hz
ul
Upper Limit Frequency 60.0 Hz
ll
Lower Limit Frequency 0.0 Hz
vl
Base Frequency 1
(Motor Nameplate Frequency)
60.0 Hz
vlv
Base Frequency Voltage 1
(Motor Nameplate Voltage)
230, 460, or 575V
pt
V/Hz Control Mode Selection 0: Constant Torque
f701
Current/Voltage Display Unit Selection 0: % 1: Amps/Volts
thr
Motor Electronic Thermal Protection
(Motor Nameplate Current)
100 %/ VFD FLA
f300
PWM Carrier Frequency 12.0 kHz
f301
Auto-Restart Control Selecon
(Catching a Spinning Motor)
0: Disabled
f303
Retry Selecon
(Automatic Reset for Non-Critical Faults)
0: Disabled
f750
Easy Key Funcon Selecon
(Setup Easy Key as Local/Remote)
0: Easy Mode Switching
0: Setting Dial 1 (saved at power off)
0: Easy/Standard Switching