7
6
ELECTRIC WIRING
n
Single outdoor unit
Voltage
Range
Compressor Fan Motor Power Supply
Heat Pump
Model
MMY-
Coolin
Onl
model
MMY-
Nominal
Volta
e
(V-Ph-Hz)
Min Max RLA LRA kW FLA MCA MOCP ICF
MAP0501HT8 MAP0501T8 400-3-50 342 457 4.0 + 4.0 0.60 0.8 16.5 20 —
MAP0601HT8 MAP0601T8 400-3-50 342 457 4.6 + 4.6 0.60 0.8 16.5 20 —
MAP0801HT8 MAP0801T8 400-3-50 342 457 5.2 + 5.2 0.60 1.0 20.0 30 —
MAP1001HT8 MAP1001T8 400-3-50 342 457 6.5 + 6.5 0.60 1.1 22.5 30 —
MAP1201HT8 MAP1201T8 400-3-50 342 457 9.5 + 9.5 0.60 1.1 24.5 30 —
n
Combination of outdoor unit
Compressor
Voltage
Range
Unit No.1 Unit No.2 Unit No.3 Unit No.4
Fan Motor Power Supply
Heat Pump
Model
MMY-
Coolin
Onl
model
MMY-
Nominal
Volta
e
(V-Ph-Hz)
Min Max RLA LRA RLA LRA RLA LRA RLA LRA kW FLA MCA MOCP ICF
AP1401HT8 AP1401T8 400-3-50 342 457 5.2 + 5.2 — 4.6 + 4.6 — — — — — 0.6 × 2 1.0 + 0.8 36.5 40 —
AP1601HT8 AP1601T8 400-3-50 342 457 5.2 + 5.2 — 5.2 + 5.2 — — — — — 0.6 × 2 1.0 + 1.0 40.0 50 —
AP1801HT8 AP1801T8 400-3-50 342 457 6.5 + 6.5 — 5.2 + 5.2 — — — — — 0.6 × 2 1.0 + 1.1 42.5 50 —
AP2001HT8 AP2001T8 400-3-50 342 457 6.5 + 6.5 — 6.5 + 6.5 — — — — — 0.6 × 2 1.1 + 1.1 45.0 60 —
AP2201HT8 AP2201T8 400-3-50 342 457 5.2 + 5.2 — 5.2 + 5.2 — 4.6 + 4.6 — — — 0.6 × 3 1.0 + 1.0 + 0.8 56.5 70 —
AP2211HT8 AP2211T8 400-3-50 342 457 9.5 + 9.5 — 6.5 + 6.5 — — — — — 0.6 × 2 1.1 + 1.1 47.0 60 —
AP2401HT8 AP2401T8 400-3-50 342 457 5.2 + 5.2 — 5.2 + 5.2 — 5.2 + 5.2 — — — 0.6 × 3 1.0 + 1.0 + 1.0 60.0 70 —
AP2411HT8 AP2411T8 400-3-50 342 457 9.5 + 9.5 — 9.5 + 9.5 — — — — — 0.6 × 2 1.1 + 1.1 49.0 60 —
AP2601HT8 AP2601T8 400-3-50 342 457 6.5 + 6.5 — 5.2 + 5.2 — 5.2 + 5.2 — — — 0.6 × 3 1.1 + 1.1 + 1.0 62.5 70 —
AP2801HT8 AP2801T8 400-3-50 342 457 6.5 + 6.5 — 6.5 + 6.5 — 5.2 + 5.2 — — — 0.6 × 3 1.1 + 1.1 + 1.0 65.0 80 —
AP3001HT8 AP3001T8 400-3-50 342 457 6.5 + 6.5 — 6.5 + 6.5 — 6.5 + 6.5 — — — 0.6 × 3 1.1 + 1.1 + 1.1 67.5 80 —
AP3201HT8 AP3201T8 400-3-50 342 457 5.2 + 5.2 — 5.2 + 5.2 — 5.2 + 5.2 — 5.2 + 5.2 — 0.6 × 4 1.0 + 1.0 + 1.0 + 1.0 80.0 90 —
AP3211HT8 AP3211T8 400-3-50 342 457 9.5 + 9.5 — 6.5 + 6.5 — 6.5 + 6.5 — — — 0.6 × 3 1.1 + 1.1 + 1.1 69.5 80 —
AP3401HT8 AP3401T8 400-3-50 342 457 6.5 + 6.5 — 5.2 + 5.2 — 5.2 + 5.2 — 5.2 + 5.2 — 0.6 × 4 1.1 + 1.0 + 1.0 + 1.0 82.5 100 —
AP3411HT8 AP3411T8 400-3-50 342 457 9.5 + 9.5 — 9.5 + 9.5 — 6.5 + 6.5 — — — 0.6 × 3 1.1 + 1.1 + 1.1 71.5 80 —
AP3601HT8 AP3601T8 400-3-50 342 457 6.5 + 6.5 — 6.5 + 6.5 — 5.2 + 5.2 — 5.2 + 5.2 — 0.6 × 4 1.1 + 1.1 + 1.0 + 1.0 85.0 100 —
AP3611HT8 AP3611T8 400-3-50 342 457 9.5 + 9.5 — 9.5 + 9.5 — 9.5 + 9.5 — — — 0.6 × 3 1.1 + 1.1 + 1.1 73.5 90 —
AP3801HT8 AP3801T8 400-3-50 342 457 6.5 + 6.5 — 6.5 + 9.5 — 6.5 + 6.5 — 5.2 + 5.2 — 0.6 × 4 1.1 + 1.1 + 1.1 + 1.0 87.5 100 —
AP4001HT8 AP4001T8 400-3-50 342 457 6.5 + 6.5 — 6.5 + 6.5 — 6.5 + 6.5 — 6.5 + 6.5 — 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 90.0 100 —
AP4201HT8 AP4201T8 400-3-50 342 457 9.5 + 9.5 — 6.5 + 6.5 — 6.5 + 6.5 — 6.5 + 6.5 — 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 92.0 110 —
AP4401HT8 AP4401T8 400-3-50 342 457 9.5 + 9.5 — 9.5 + 9.5 — 6.5 + 6.5 — 6.5 + 6.5 — 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 94.0 110 —
AP4601HT8 AP4601T8 400-3-50 342 457 9.5 + 9.5 — 9.5 + 9.5 — 9.5 + 9.5 — 6.5 + 6.5 — 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 96.0 110 —
AP4801HT8 AP4801T8 400-3-50 342 457 9.5 + 9.5 — 9.5 + 9.5 — 9.5 + 9.5 — 9.5 + 9.5 — 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 98.0 110 —
NOTE :Legend MCA
MOCP
ICF
RLA
: Minimum Circuit Amps
: Maximum Overcurrent Protection (Amps)
: Maximum Instantaneous Current Flow Start
: Rated Load Amps
LRA
FLA
kW
: Locked Rotor Amps
: Full Load Amps
: Fan Motor Rated Output (kW)
RLA is based on the following conditions.
Indoor temperature : 27°C DB/19°C WB
Outdoor temperature : 35°C DB
50Hz