18
Change of indoor address from wired remote controller
To change the indoor address in individual operation (Wired remote controller : Indoor unit = 1 : 1) or
group control (When the setup operation with automatic address has finished, this change is available.)
<Procedure> (Operation while air conditioner stops)
1
Push simultaneously
SET
+
CL
+ buttons for 4 seconds or more.
(The firstly displayed unit No indicates the header unit in group control.)
2
In group control, select an indoor unit No to be changed by
UNIT
button.
(The fan of the selected indoor unit is turned on.)
3
Using the setup temp. / buttons, set 13 to the item code.
4
Using the timer time / buttons, change the displayed setup data to a data which you
want to change.
5
Push
SET
button.
6
Using the
UNIT
button, select the unit No. to be changed at the next time.
Repeat the procedure
4
to
6
and change the indoor address so that it is not duplicated.
7
After the above change, push
UNIT
button to confirm the changed contents.
8