E6581611
F-19
6
1) Constant torque characteristics
Setting of V/F control mode selection  to (V/F constant)
This is applied to loads with equipment like conveyors and cranes that require the same torque at low
speeds as at rated speeds.
Output voltage(%)
Base frequency voltage

Output frequency (Hz)

Base frequency

0
* To increase the torque further, increase the setting value of the manual torque boost value 1 ().
Refer to section 6.4 for details.
2) Setting for fans and pumps
Setting of V/F control mode selection  to (variable torque)
This is appropriate for load characteristics of such things as fans, pumps and blowers in which the torque is
proportional to the square of load rotation speed.
.
Output voltage(%
)
Base frequency voltage


Base frequency

0
Output frequency (Hz)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net