E6581611
F-144
6
Title Function Adjustment range Default setting
f910
Step-out detection current level 1 - 150 (%) 100
f911
Step-out detection time
0.00: No detection
0.01
-2.55 (s)
0.00
f912
q-axis inductance
0.01-650.0 (mH) 10.00
f913
d-axis inductance
0.01-650.0 (mH) 10.00

Factory specific coefficient 9L
--
Refer to section 6.25.2 about setting motor constants.
Note 1: When using an PM motor, consult your Toshiba distributor, since the inverter is not compatible with all
types of PM motors.
Note 2: The inverter may fail to detect step-out in some cases, because it uses an electrical method to detect
step-out. To avoid detection failures, you are recommended to install a mechanical step-out detector.
6.40 Traverse function
f980 : Traverse selection
f981 : Traverse acceleration time
f982 : Traverse deceleration time
f983 : Traverse step
f984 : Traverse jump step
Refer to “Traverse control Instruction Manual : E6581877” for details.
4
20
(mA)
0
0
20
(mA)
0
4
20
(mA)
0
0
20
(mA)
01
アナログ出力電流
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VFS15-4037PL-W and is the answer not in the manual?

Toshiba TOSVERT VFS15-4037PL-W Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VFS15-4037PL-W
CategoryInverter
LanguageEnglish

Related product manuals