E6581611
F-62
6
[If momentary power failure occurs]
An example of setting when f302=2
Motor speed
Time
In
p
ut volta
g
e
Deceleration stop
• Even after the recovery from an input power failure, the motor continues deceleration stop. If the voltage in the
inverter main circuit falls below a certain level, however, control will be stopped and the motor will coast.
• If the voltage in main circuit falls below main circuit undervoltage (moff) level at Non-stop control during power
failure, the motor will coast and inverter displays stop and 0.0 alternately. The motor continues coasting even
after power supply is restored.
Motor speed
In
p
ut volta
g
e
Note 5: If momentary power failure occurs during deceleration stop,
p
ower ride-throu
g
h control will not be
p
erformed.
Internal DC
voltage level
Normal acceleration
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VFS15-4037PL-W and is the answer not in the manual?

Toshiba TOSVERT VFS15-4037PL-W Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VFS15-4037PL-W
CategoryInverter
LanguageEnglish

Related product manuals