E6581611
K-16
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0510 Acceleration time 3 s 0.1/0.1 0.0-3600 (360.0) *8 10.0 6.27.2
0511 Deceleration time
3
s 0.1/0.1 0.0-3600 (360.0) *8 10.0
0512 Acceleration/decel
eration 3 pattern
- - 0: Linear
1: S-pattern 1
2: S-pattern 2
0
0513 Acceleration/decel
eration 2 and 3
switching
frequency
Hz 0.1/0.01 0.0 (disabled)
0.1-
0.0
0515 Deceleration time
at emergency stop
s 0.1/0.1 0.0-3600 (360.0) *8 10.0 6.29.4
0519 Setting of
acceleration/decel
eration time unit
- - 0: -
1: 0.01s unit (after execution: 0)
2: 0.1s unit (after execution: 0)
0 5.2
6.27.2
0590 Shock monitoring - - 0: Disabled
1: Current detection
2: Torque detection
0 6.28
0591 Shock monitoring
trip/alarm
selection
- -
0: Alarm only
1: Tripping
0
0592 Shock monitoring
detection direction
selection
- - 0: Over-current / torque detection
1: Low-current / torque detection
0
0593 Shock monitoring
detection level
% 1/0.01 0-250 150
0595 Shock monitoring
detection time
s 0.1/0.1 0.0-10.0 0.5
0596 Shock monitoring
detection
hysteresis
% 1/0.01 0-100 10
0597 Shock monitoring
detection start
waiting time
s 0.1/0.1 0.0-300.0 0.0
0598 Shock monitoring
detection action
selection
- - 0: During operation
1: During operation (except
acceleration / deceleration)
0
*8: These parameters can be changed to 0.01s unit by setting f519=1.