E6581611
E-12
5
= (150%-60s), = (Constant torque characteristic)
Protection is given uniformly regardless of temperature, as shown by the 150%-60 sec overload curve in the
figure below.
Inverter overload protection characteristics
= (Temperature estimation), = (Constant torque characteristic)
This parameter adjusts automatically overload protection, predicting the inverter internal temperature rise.
(diagonally shaded area in the figure below)
Inverter overload protection characteristics
60
100%: Inverter rated output current
time [s]
Inverter overload
Monitored output current [%]
0
110% 150%
Current
[%]
Inverter overload time [s]
(Outline data)
111 2400
120 240
130 120
140 80
150 60
185 2
200 0.5
time [s]
f631=0
60
0
110%
150%
Monitored output current [%]
100%: Inverter rated output current