E6581611 
E-2 
5 
  Adjustment scale with parameter  (Meter adjustment) 
Connect meters as shown below. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 [Example of how to adjust the FM terminal frequency meter] 
 
* Use the meter's adjustment screw to pre-adjust zero-point. 
* Adjust f691 and f692 in advance in case of 4-20mA output. 
Operation panel action  LED display Operation 
-  .  
Displays the output frequency. 
(When standard monitor display selection  is set to ) 
 
 
The first basic parameter “” (history function) is displayed. 
 
 
Turn the setting dial to select . 
 
.  
Output frequency can be displayed by pressing the center of the 
setting dial. 
 
.  
Turn the setting dial to adjust the meter. 
The meter’s indicator will change by turning setting dial. 
(The inverter displays output frequency and it will not change with the 
setting dial) 
 
 
 
 
 
 ⇔ 
 
Press the center of the setting dial to save the meter's adjustments. 
 and the frequency are displayed alternately.  
 
 +  .  
The display returns to displaying output frequency. 
(When standard monitor display selection  is set to  
[output frequency]) 
FM 
CC 
 =  
Inverter 
FM 
CC 
Inverter 
The reading of the  
meter will fluctuate 
during scale 
adjustment. 
= 
The reading of the 
meter will 
fluctuate during 
scale adjustment. 
+ 
- 
+
* Optional QS-60T frequency 
meter is available. 
* Meter with a maximum  
scale of 1.5x the inverter's  
rated output current is 
recommended. 
<Displaying output frequency> 
<Displaying output current> 
MODE 
MODE MODE 