E6581611 
E-3 
5 
  Example of 4-20mA output adjustment (Refer to section 6.33.3 for details) 
 
=1, =0  =1, =20 
 
 
Output 
currrent 
Output 
currrent
Internal calculated value
Internal calculated value 
0
20
(mA)
0 100%
4
20
(mA)
0 100%
f692
fm
fm
 
Note 1) When using the FM terminal for current output, be sure that the external load resistance is less than 600Ω. 
Use over 1kΩ external load resistance for voltage output. 
Note 2)  =  is the motor drive frequency. 
  Adjusting the meter in inverter stop state 
  Adjustment of the meter for output current (=1) 
Adjustment of the meter for output current can be done in inverter stop state. 
When setting  to  for fixed output 1 (output current 100% equivalent), a signal assuming that 
inverter rated current (output current 100% equivalent) passes will be output from the FM terminal.  
Adjust the meter with the  (Meter adjustment) parameter in this state. 
Similarly, if you set  to  for fixed output 2 (output current 50% equivalent), a signal assuming 
that 50% of inverter rated current (output current 50% equivalent) passes will be output from the FM 
terminal. 
After meter adjustment is ended, set  to  (output current). 
 
 Other adjustments ( = ,  to7, 9 to, , ,  to ) 
 = : When fixed output 3 (other than the output current) is set, a signal of the value for other 
monitors is fixed at the following values and output through the FM terminal. 
100% standard value for each item is the following: 
=0, 2, 12,   : Maximum frequency (h) 
=3, 4  : 1.5 times of rated voltage 
=7  : 2.5 times of rated torque 
=9 to11  : Rated load factor 
=13, ,  : Maximum input value (10V, or 20mA) 
=18  : Maximum value (100.0%) 