DC Inverter U-match Series for R410A Unitary Split Air Conditioner
31
4.4.1.4 Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures. If a fault exists that could
compromise safety, then no electrical supply shall be connected to the circuit until it
is satisfactorily dealt with. If the fault cannot be corrected immediately but it is
necessary to continue operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
(1) That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking.
(2) That no live electrical components and wiring are exposed while charging,
recovering or purging the system.
(3) That there is continuity of earth bonding.
4.4.2 Repairs to Sealed Components
4.4.2.1 Electrical Safety
From the equipment being worked upon prior to any removal of sealed covers,
etc. If it is absolutely necessary to have an electrical supply to equipment during
servicing, then a permanently operating form of leak detection shall be located at
the most critical point to warn of a potentially hazardous situation.
4.4.2.2 Particular Attention
Electrical components, the casing is not altered in such a way that the level of
protection is affected. This shall include damage to cables, excessive number of
connections, terminals notmade to original specification, damage to seals, incorrect
fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no
longer serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer’s specifications.
The use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior
to working on them.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tosot U-match Series and is the answer not in the manual?

Tosot U-match Series Specifications

General IconGeneral
BrandTosot
ModelU-match Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals