ECON JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to ECON, the corresponding MISC screw
terminal on the backplate will be connected to an economizer.
ECONOMIZER OPERATION - If your HVAC unit is equipped with an
economizer system, the thermostat will provide power to the MISC1, MISC2,
or MISC3 terminal of the thermostat when the thermostat is in an occupied
time period. The MISC1, MISC2, or MISC3 terminal will be de-energized
when the thermostat is in an unoccupied time period.
Y2 JUMPER SETTING
If the jumper for MISC1 is set to Y2 the MISC1 screw terminal on the backplate will control a
second stage of cooling.
Y2 OPERATION - SECTION 12
Page 16.4
Explanation of Jumper Settings (continued)Explanation of Jumper Settings (continued)
The 2nd Stage of heat or cool is
(A) The 1st Stage has been on for the two minutes.
(B) The temperature spread
than: the setpoint
turned on when:
from the setpoint is equal to or greater
plus the 1st stage deadband (step #19, page
12.5), plus two degrees.
And
Cool
Setpoint
DeadbandDeadband
db 1 db 2
(adj. 0-10 )(adj. 1-6 )
1st Stage
turn on
2nd Stage
turn on
Cooling
TEMPERATURE
INCREASE