● Air supply diffusers must be selected and located carefully. They must be sized and positoined to deliver treated air along the
perimerter of the space. If they are too small for their intended airflow, they become noisy. If they are not located properly, they
cause drafts. Return air grilles must be properly sized to carry air back to the blower. If they are too small, they also cause noise.
● The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures
a comfortable living space.
● An air velocity meter or airflow hood can give a reading of system CFM.
During installation, installer should select the air speed according to the actual setting static pressure. Please refer to the
Table 7-1 AIRFLOW PERFORMANCE DATA
Table 7-3 Electric Heat Pressure Drop Tables(IN.W.C)
Small Cabinet:24K,30K,36K
5kW
7.5kw
10kW
15kW
900
0.05
0.05
0.05
/
1000
0.05
0.05
0.05
/
1100
0.05
0.05
0.05
0.1
1200
0.05
0.05
0.05
0.1
1300
0.05
0.05
0.05
0.1
1400
0.1
0.1
0.1
0.1
STATIC
STANDARD CFMSCFM
Large Cabinet:42K,48K,60K
5kW
7.5kw
10kW
15kW
20kW
1500
0.1
0.1
0.1
/
/
1600
0.1
0.1
0.1
/
/
1700
0.1
0.1
0.15
0.2
0.2
1800
0.1
0.1
0.15
0.2
0.2
1900
0.15
0.15
0.15
0.2
0.2
2000
0.15
0.15
0.15
0.2
0.2
2100
0.15
0.15
0.15
0.2
0.2
2200
0.15
0.15
0.15
0.2
0.25
STATIC
STANDARD CFMSCFM
Table 7-4 Refrigerant charge for H/P system
165
161
157
153
149
145
141
137
133
129
125
121
117
113
109
105
256
251
246
241
236
231
226
221
216
211
282
279
275
272
268
264
260
256
252
248
244
240
236
303
300
297
294
291
287
284
280
276
272
268
264
260
256
252
248
316
313
310
307
304
300
297
293
289
285
281
277
273
269
265
261
328
325
322
319
316
312
309
305
301
297
293
289
285
281
277
273
350
346
342
339
335
331
328
324
321
317
313
309
305
301
297
293
370
366
362
358
353
349
346
343
340
336
332
328
324
320
316
312
400
394
389
384
374
370
368
365
361
357
353
349
345
341
337
333
426
421
415
410
399
393
389
386
382
378
374
370
366
362
358
354
446
440
434
428
419
416
413
410
406
403
399
395
392
388
385
381
465
459
453
446
443
440
437
434
430
427
423
420
417
414
411
408
487
481
476
471
468
465
462
459
455
451
447
444
440
437
433
429
508
503
499
496
493
490
486
483
479
475
471
467
463
459
455
450
Cooling Charge Chart/Tableau De Charge de Refroidissement24
Cooling Mode
Mode
De Refroidissement
Outdoor Ambient Temperature(oF)/Temperature Amdiante Exterieure(en oF)
Low Pressure Service Port(psig)
Vanne Détectée de Pression Basse(en psig)
High Pressure Service Port (psig)/Vanne Détecté de Pression Haute(en psig)
55 60 65 70 75 80 85 90 95 100 105 110 115