Trane 22 Series - Refrigerant Connection and Charging; Outdoor Unit Valve Torque Specifications

Trane 22 Series
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
22 Series Multi-Zone
Refrigerant Piping at the Indoor Units
Reference the Indoor Unit Installation Guide
Refrigerant Piping at the Outdoor Unit
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. Follow the flare nut
guidelines in this manual.
Torque Reference Table
Pipe Diameter in. (mm) Tube Thickness in. (mm) Tightening Torque
1/4" (6.35) 0.03 (0.8)
11.25 - 14.75 lb•ft (15 ~ 20 N•m)
3/8" (9.52) 0.03 (0.8)
22.25 - 29.50 lb•ft (30 ~ 40 N•m)
1/2" (12.7) 0.03 (0.8)
33.25 - 40.50 lb•ft (45 ~ 55 N•m)
5/8" (15.9) 0.04 (1.0)
44.25 - 47.75 lb•ft (60 ~ 65 N•m)