18 MS-SVN056C-EN
Cassette Unit Installation
Distribution ductwork installation
Model 18 to 24 Series A = 160mm; Series B = 75mm
Model 36 to 60 Series A = 160mm; Series B = 95mm
Single duct connection
Ductwork air volume is approximately 300-360m3/h - Model 18 to 24
Ductwork air volume is approximately 400-640m3/h - Model 36 to 60
Maximum duct length is 2m.
In the case of double duct connection, the original opening for outgoing air with the same piping direction, must
be sealed.
Double duct connection
Ductwork air volume is approximately 200-260m3/h - Model 18 to 24
Ductwork air volume is approximately 300-500m3/h - Model 36 to 60
Maximum duct length is 1.5m for a single duct.
The original opening for outgoing air with the same piping direction, must be sealed.
One way
Two ways