Model Number | 4PXCBU36BS3HAC |
---|---|
Category | Chiller |
Cooling Capacity | 36, 000 BTU/H |
Refrigerant Type | R-410A |
Compressor Type | Scroll |
Phase | 1 |
Voltage | 208-230V |
This coil is designed for use with a heat pump or cooling outdoor section using R-410A REFRIGERANT.
The 4PXC equipment has been evaluated for "Suitable for Mobile Home use". Height of Furnace, Coil, and duct work must be 7 ft. or less.
The coil MUST be installed downstream (in the outlet air) of the furnace.
Use Installer's Guide packaged with furnaces, outdoor sections, and thermostat for physically installing those components.
This coil is pressurized with 8-12 psig of dry air. Do not stand directly in front of coil connections when removing sealing plugs.
When used with a downflow furnace, a subbase is not required between the coil case and combustible flooring.
Recommended for humid applications to prevent water formation on the bottom of the drain pan.
Do NOT open refrigerant valve until lines and coil are brazed, evacuated, and leak checked to prevent contamination.
Flow nitrogen during brazing, use good technique, minimize sharp bends, insulate suction line, protect TXV bulb.
Pressurize lines and coil to 150 PSIG with nitrogen, leak check with soap bubbles, repair leaks.
Drain hole must be cleared of insulation. Insulate primary drain line to prevent sweating.
Wipe down foil-covered insulation. Use water to wash away debris; remove coil for heavy contamination.
Flowchart to diagnose issues with superheat, subcooling, airflow, and TXV performance in cooling mode.