IMPORTANTThis document contains a wiring diagram, a parts list, and service information. This is customer property
and is to remain with this unit. Please return to service information pack upon completion of work.
WARNING
!
THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS
POSSESSING ADEQUATE BACKGROUNDS OF ELECTRICAL AND
MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR
CONDITIONING PRODUCT MAY RESULT IN PERSONAL INJURY AND
OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT
BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION,
NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.
CAUTION
!
RECONNECT ALL GROUNDING DEVICES.
ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING
ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING
WIRES, SCREWS, STRAPS, CLIPS, NUTS OR WASHERS USED
TO COMPLETE A PATH TO GROUND ARE REMOVED FOR
SERVICE, THEY MUST BE RETURNED TO THEIR ORIGINAL
POSITION AND PROPERLY FASTENED.
WARNING:
HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE
CAPACITORS BEFORE SERVICING
© 2013 Trane
NOTICE: The manufacturer has a policy of continuous product and product data improvement
and it reserves the right to change design and specifications without notice.
Service Facts
CAUTION
!
UNIT CONTAINS R-410A REFRIGERANT!
R-410A OPERATING PRESSURE EXCEEDS THE
LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS
REQUIRED. FAILURE TO USE PROPER SERVICE
TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR
PERSONAL INJURY.
SERVICE
USE ONLY R-410A REFRIGERANT AND
APPROVED POE COMPRESSOR OIL.
PRODUCT SPECIFICATIONS
OUTDOOR UNIT 12
POWER CONNS. — V/PH/HZ 3
MIN. BRCH. CIR. AMPACITY
BR. CIR. PROT. RTG. – MAX. (AMPS)
COMPRESSOR
NO. USED - NO. SPEEDS
VOLTS/PH/HZ
R.L. AMPS 7 - L.R. AMPS
FACTORY INSTALLED
START COMPONENTS 8
INSULATION/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN
DIA. (IN.) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G. 4
NO. MOTORS - HP
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT
LBS. — R-410A (O.D. UNIT) 5
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS 6
LINE SIZE - IN. O.D. LIQ. 6
CHARGING SPECIFICATION
SUBCOOLING
DIMENSIONS
CRATED (IN.)
WEIGHT
SHIPPING (LBS.)
NET (LBS.)
4TTA3-SF4-1A
Split System
Cooling
4TTA3030A4000C, 4TTA3036B4000A
01/13
Tubing lengths in excess of sixty (60) feet see application software.
CAUTION
!
DISCONNECT ALL POWER TO COMPRESSOR WHEN
COMPRESSOR MOTOR ROTATION IS REVERSED. CHANGE
ANY TWO CUSTOMER POWER LEADS TO CORRECT ROTATION.
Failure to change customer power leads to correct compressor
rotation may result in compressor damage during operation.
COMPRESSOR MOTOR ROTATION
HOT SURFACE! DO NOT TOUCH TOP OF COMPRESSOR.
May cause minor to severe burning.
CAUTION
!
CONTAINS REFRIGERANT!
SYSTEM CONTAINS OIL AND REFRIGERANT UNDER
HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE
PRESSURE BEFORE OPENING SYSTEM.
Failure to follow proper procedures can result in personal
illness or injury or severe equipment damage.
CAUTION
!
4TTA3036B4000A
460/3/60
8
15
SCROLL
1 - 1
460/3/60
5.8 - 38
NO
NO
YES
PROPELLER
23 - 1
DIRECT - 1
2800
1 - 1/8
825
460/3/60
.40
SPINE FIN™
1 - 24
12.89
3/8
5 LBS., 12 OZ.
YES
3/4
3/8
10°F
H X W X D
34 x 30.1 x 33
176
149
4TTA3030A4000C
460/3/60
5
15
RECIP
1 - 1
460/3/60
3.7 - 28
NO
NO
YES
PROPELLER
23 - 1
DIRECT - 1
3150
1 - 1/8
825
460/3/60
.40
SPINE FIN™
1 - 24
18.75
3/8
5 LBS., 11 OZ.
YES
3/4
3/8
10°F
H X W X D
38 x 30.1 x 33
222
195
1 Certified in accordance with the Air-Source Unitary Air-conditioner Equipment
certification program, which is based on AHRI standard 210/240.
2 Rated in accordance with AHRI standard 270.
3 Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or
fuses.
4 Standard Air — Dry Coil — Outdoor
5 This value approximate. For more precise value see unit nameplate.
6 Max. linear length 60 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid 60 ft.
For greater length consult refrigerant piping software Pub. No. 32-3312-0*
(* denotes latest revision).
7 This value shown for compressor RLA on the unit nameplate and on this specification
sheet is used to compute minimum branch circuit ampacity and max. fuse size. The
value shown is the branch circuit selection current.
8 No means no start components. Yes means quick start kit components. PTC means
positive temperature coefficient starter.
20’
30’
40’
50’
60’
3/4”
3/4”
3/4”
3/4”
3/4”
3/8”
3/8”
3/8”
3/8”
3/8”
3 oz.
9 oz.
14 oz.
20 oz.
26 oz.
Additional
Refrigerant
TUBING INFORMATION
Tubing
Length
Tubing Sizes
Liquid
Suction
Question and Answer IconNeed help?

Do you have a question about the Trane 4TTA3030A4000C and is the answer not in the manual?

Overview

This document describes the 4TTA3-SF4-1A series of split system cooling units, specifically models 4TTA3036A4000C and 4TTA3036B4000A. These units are designed for residential and light commercial applications, providing cooling functionality.

Function Description:

The 4TTA3-SF4-1A series units are part of a split system, meaning they consist of an outdoor unit (the subject of this manual) and an indoor unit (not detailed here, but necessary for a complete system). The primary function is to provide cooling by circulating refrigerant. The system utilizes a compressor, outdoor coil, and an expansion device (either an expansion valve or a fixed orifice) to facilitate the refrigeration cycle.

Important Technical Specifications:

The units operate on a 208/230V, 60Hz, single-phase power supply.

Model-Specific Data:

  • 4TTA3036A4000C:

    • Outdoor Unit Type: Coil
    • Face Area (Sq. Ft.): 18.75
    • Tube Rows: 2
    • Refrigerant: R-410A
    • Liquid Line O.D. (In.): 3/8
    • Suction Line O.D. (In.): 7/8
    • Charging Specification: 10 F
    • Dimensions (H x W x D): 38 x 30.1 x 33 inches
    • Shipping Weight (Lbs.): 222
    • Net Weight (Lbs.): 195
  • 4TTA3036B4000A:

    • Outdoor Unit Type: Coil
    • Face Area (Sq. Ft.): 12.89
    • Tube Rows: 3
    • Refrigerant: R-410A
    • Liquid Line O.D. (In.): 3/8
    • Suction Line O.D. (In.): 7/8
    • Charging Specification: 10 F
    • Dimensions (H x W x D): 34 x 30.1 x 33 inches
    • Shipping Weight (Lbs.): 176
    • Net Weight (Lbs.): 149

Electrical Data (for both models):

  • Power Conn. - V/Ph/Hz: 208/230V, 1 Phase, 60Hz
  • Min. Circ. Amps (MCA): 15
  • Max. Overcurrent Protection (MOP): 25
  • Compressor: Reciprocating
  • Fan Speed: 1
  • Volts/Hz/Ph: 208/230V, 60Hz, 1 Phase
  • Min. Amps - L.R. Amps: 47 / 28
  • Factory Installed:
    • Start Components: No
    • Insulation/Sound Blanket: No
    • Compressor Heat: No
  • Outdoor Fan: Propeller
  • Outdoor Fan Dia. (In.): 23
  • Type Drive - No. Speeds: Direct - 1
  • CFM @ 0.0 In. W.G.: 3100
  • HP/RPM/Volts: 1/4 HP, 825 RPM, 208/230V
  • Min. Amps: 40

Refrigerant Circuit:

The units use R-410A refrigerant. The refrigerant circuit includes an outdoor coil, compressor, drier, and an expansion device. For field-installed interconnecting tubing, the liquid line is 3/8" O.D. and the suction line is 7/8" O.D. Pressure taps are provided for checking system pressures.

Usage Features:

  • R-410A Refrigerant: These units utilize R-410A refrigerant, which requires specific handling procedures. Only R-410A refrigerant and approved POE compressor oil should be used.
  • Subcooling Charging: The manual provides detailed instructions and charts for subcooling charging, which is critical for optimal performance. The target subcooling value depends on the liquid line temperature and liquid line pressure.
  • System Compatibility: The units are designed for use with TXV indoor systems. The benefits of installing approved indoor and outdoor split systems are maximum efficiency, optimum performance, and the best overall system reliability.
  • Thermostat Compatibility: The system requires a compatible room thermostat for operation.

Maintenance Features:

  • Troubleshooting Flowcharts: The manual includes comprehensive troubleshooting flowcharts for common issues such as "Compressor fails to start" and "Compressor won't run." These flowcharts guide technicians through diagnostic steps, including checking contactors, voltage, resistance, and start components.
  • Wiring Diagrams: Detailed schematic and wiring diagrams are provided to aid in installation, troubleshooting, and maintenance. These diagrams illustrate the electrical connections for components like the compressor, fan motor, contactor, and control circuits.
  • Pressure Tables: Pressure tables for 4TTA304 with TXC***BC cooling with thermal expansion valve are included, providing expected liquid pressure (PSIG) and suction pressure (PSIG) based on outdoor temperature and indoor wet bulb temperature. These tables are essential for accurate system charging and performance verification.
  • Refrigerant Circuit Diagram: A diagram of the refrigerant circuit helps in understanding the flow of refrigerant and identifying components for service.
  • Safety Warnings: The manual emphasizes several safety warnings:
    • R-410A Refrigerant Caution: Units contain R-410A refrigerant. Exceeding the limit of R-410A operating pressure can result in equipment damage or personal injury. Proper service tools and procedures are required.
    • Compressor Start Rotation Caution: Disconnect all power to the compressor when connecting two compressor leads to prevent incorrect rotation. Incorrect rotation may result in compressor damage.
    • Hot Surface Caution: Do not touch the top of the compressor, as it may be hot and cause burns.
    • Refrigerant Contains Refrigerant Caution: System contains liquid and vapor refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. Failure to follow proper procedures can result in personal injury.
    • Electrical Hazard Warning: Disconnect all grounding devices. Electrical currents are grounded through wires, screws, straps, clips, nuts, or washers used to secure parts. These items must be returned to their original position and properly fastened.
    • General Warning: Hazardous voltage. Disconnect all electric power before servicing. Failure to disconnect power before servicing can result in severe personal injury or death.
    • General Caution: Unit terminals are not designed to be used as a step. Failure to do so may cause damage to the equipment.

Important Notes for Installation and Service:

  • Power Supply: Ensure the power supply matches the unit's requirements.
  • Wiring: All wiring must comply with local codes.
  • Thermostat Wiring: Specific instructions are provided for connecting the thermostat, including jumper settings for different control scenarios.
  • Optional Components: The manual mentions optional components like a low-pressure cut-out (LPCO) and high-pressure cut-out (HPCO).
  • Manufacturer's Policy: The manufacturer has a policy of continuous product and data improvement and reserves the right to change design and specifications without notice.

Trane 4TTA3030A4000C Specifications

General IconGeneral
BrandTrane
Model4TTA3030A4000C
CategoryAir Conditioner
LanguageEnglish

Related product manuals