18-AC78D1-6 3
LIFT
When mounting the outdoor unit on a roof, be
sure the roof will support the unit’s weight.
Properly selected isolation is recommended to
prevent sound or vibration transmission to the
building structure.
Maximum line length = 100 feet.
Maximum vertical length = 60 feet.
Compressor crankcase heat is required for line
lengths over 60 feet.
Use only the line diameters indicated in Table
5.1.
LIFT
Section 2. Unit Location Considerations
2.1 Unit Dimensions and Weight
2.2 Refrigerant Piping Limits
Unit Dimensions and Weight
Models H x D x W Weight*
4TTM3018-036 28-7/8 x 23-1/2 x 25-1/2 154
4TTM3042-060 28-7/8 x 28-1/2 x 29-1/4 168
* Weight values are estimated.
Standard Line
Set 100Max
Line Length
60’ Max
Line Lift
60’ Max
Line Lift