152
Address Setting-Umatch ODU
SW6 dip switch setting
Unit address for
central control
SW6-1 SW6-2 SW6-3 SW6-4 SW6-5 SW6-6 SW6-7 SW6-8
0 0 0 0 0 0 0 0 Address 0
0 0 0 0 0 0 0 1 Address 1
0 0 0 0 0 0 1 0 Address 2
0 0 0 0 0 0 1 1 Address 3
0 0 0 0 0 1 0 0 Address 4
0 0 0 0 0 1 0 1 Address 5
0 0 0 0 0 1 1 0 Address 6
0 0 0 0 0 1 1 1 Address 7
0 0 0 0 1 0 0 0 Address 8
0 0 0 0 1 0 0 1 Address 9
0 0 0 0 1 0 1 0 Address 10
0 0 0 0 1 0 1 1 Address 11
0 0 0 0 1 1 0 0 Address 12
…… …..
1 1 1 1 1 1 1 1 Address 256
Indoor unit Central Control Address
Set Address by Outdoor PCB Indoor connect port
3U*** A B C
4U*** A B C D
5U*** A B C D E
4 3 2 1
Indoor central control address
SW06
0 0 0 0 1 2 3 4 5
0 0 0 1 6 7 8 9 10
0 0 1 0 11 12 13 14 15
0 0 1 1 16 17 18 19 20
0 1 0 0 21 22 23 24 25
0 1 0 1 26 27 28 29 30
0 1 1 0 31 32 33 34 35
0 1 1 1 36 37 38 39 40
1 0 0 0 41 42 43 44 45
1 0 0 1 46 47 48 49 50
1 0 1 0 51 52 53 54 55
1 0 1 1 56 57 58 59 60
1 1 0 0 61 62 63 64 65
1 1 0 1 66 67 68 69 70
1 1 1 0 71 72 73 74 75
1 1 1 1 76 77 78 79 80
Address Setting-Multi ODU