153
Remote
CN13
CN13
WHITE
Indoor unit pcb
0151800244A
YCJ-A002
A
B
YELLOW
RED
CN1
HC-SA164DBT
COMM
GND
COM1
12V
A2
B2
Control With TCONTADPYCJA2A
Connect to Umatch/Multi indoor unit by the Remote port
SW1(1 mean ON, 0 mean OFF) Definition: unitary air
conditioner
[1] [2] [3] [4] [5] [6] [7] [8]
- 0 0 0 0 0 0 0 Single mode address =1
- 0 0 0 0 0 0 1 Single mode address =2
- -- -- -- -- ----
- 0 1 0 0 1 1 0 Single mode address =39
- 0 1 0 0 1 1 1 Single mode address =40
- -- -- -- -- ----
- 0 1 1 1 1 1 1 Single mode address =63
- 1 0 0 0 0 0 0 Single mode address =64
- -- -- -- -- ----
- 1 1 1 1 1 1 0 Single mode address =127
- 1 1 1 1 1 1 1 Single mode address =128
Set Single Split address by SW1 of TCONTADPYCJA2A
For TCONTCCMYCZG1, the range of address is “1-32”