A5HL5-SF-1A-EN
21
High Pressure (MPa) Volts DC
1.6 1.89
1.5 1.80
1.4 1.72
1.3 1.63
1.2 1.54
1.1 1.46
1 1.37
0.9 1.28
0.8 1.20
0.7 1.11
0.6 1.02
0.5 0.93
0.4 0.85
0.3 0.76
0.2 0.67
0.1 0.59
0 0.50
A working High Pressure Sensor is required for the
following:
Start Up (Pressure Limits)
High Pressure
Outdoor EEV Control (Target Super Heat)
Diagnostics; Charge Level
Indoor/Outdoor Airflow
The High Pressure Transducer control is measured
across wire white and black of pin SHP. and has an
active 0-4.9VDC transducer input for sensing high
pressure.
DESCRIPTION WIRE COLOR
4.9VDC POWER RED
OUTPUT WHETE
COMMON BLACK
SSEENNSSOORRSS