EasyManua.ls Logo

Trane ACONT900AC43UA - Minimum flame current level; Causes of low flame current level

Trane ACONT900AC43UA
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GF - F 3
Measuring Flame Current
The AC potential creates a current flow in two direc-
tions. The current flow is greater in one direction
than the other (Figure 5.)
Figure 5
Electrical current flow back on the wire that connects
the flame rod to the furnace control board is a DC
current that is very low. Typical ranges of the flame
current will be from around 1.8 DC microamps to up
to 4 DC microamps (Figure 6.)
Figure 6
Minimum flame current level
The IFC needs a minimum of 1 DC microampere of
flame current to confirm the presence of burner flame.
If the IFC does not detect adequate flame current, a
retry for ignition sequence will be initiated. After a pre-
determined number of failed attempts at detecting
flame, the furnace control will lock out. The LED on
the furnace control board will flash a 2 code and the
comfort control will display alert code 20 .
Troubleshooting
Causes of low flame current level
Dirty flame rod (Figure 7) (Clean the flame rod
with metallic abrasive)
Poor furnace ground.
Poor burner ground to furnace.
Dirty
Flame Rod
Figure 7
Cracked ceramic insulator on flame rod assem-
bly (Figure 8.)
Broken wire between flame rod and furnace con-
trol board (Figure 8.)
Broken
Wire
Cracked
Ceramic
Insulator
Figure 8

Table of Contents

Related product manuals