EasyManua.ls Logo

Trane ACONT900AC43UA - Indoor Serial Port Variable Speed Blower Motor Test

Trane ACONT900AC43UA
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GF - H 4
Indoor Blower Motor
Indoor Serial Port Variable Speed Blower
Motor Test
Step 1
Is the line voltage to the blower motor high volt-
age plug pin #4 and pin #5 correct? (Figure 7)
Furnace blower motor correct voltage is 120 volts AC
and a factory jumper wire must be present connecting
pin #1 and pin #2 together.
Air Handlers blower motor correct voltage is 240 volts
AC and there is no jumper wire connecting pin #1 and
pin #2 together.
Yes: Go to Step 2.
No: Correct line voltage fault.
Figure 7
Step 2
Disconnect the blower motor’s low voltage harness
from the furnace’s IFC or the air handler’s control board
(Figure 8).
Furnace IFC plug is E8.
Air handler’s plug is VS-COMM
Figure 8
Step 3
Jumper 24 volts A/C into pin #3 and #4 in the blower
motor low voltage plug removed from the furnace IFC
or the air handler control board (Figure 9). The blower
motor should run after a short delay. The blower mo-
tor should run at 75% of its programmed torque. Does
the blower motor run?
Yes:
Furnace. Replace the furnace IFC.
Air Handler. Check the Air Handler’s control setup.
If the Air Handler is connected to a communicating
thermostat the Air Handler control must be set up for
a communicating system not a 24 volt AC control
system. If the Air Handler control setup is correct,
replace the Air Handler control board.
No: Go to Step 4.

Table of Contents

Related product manuals