RT-SVX060D-GB
24
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Installation
Gas Pipework Installation
Installation of gas piping (to be performed
by the contractor)
The installation rules for public buildings shall be
followed: refer to the brochure in the “Journal Ofciel”
number 1477-1 (France only).
The gas supply piping and the gas stop valve shall be
dimensioned to guarantee the gas supply pressure at the
unit’s inlet when it is functioning at full capacity.
It is recommended to install one expansion valve as
close as possible to each installed unit. The piping must
be self-supporting before the nal branch connection
to the unit. Allow for a dust trap (lter) upstream of the
connection to the unit. Search for gas pipe leaks using
tensio-active product such as “Teepol” or “1000 bulles”
or another equivalent method. Soapy water must not be
used.
WARNING!
Never use a ame to search for leaks. The required gas
pressures at the unit’s inlet connection are specied
in table «Marking Category of gas section in different
countries»
CAUTION!
The piping must not exert any stress on the branch
connection to the burner.
The heating system must be isolated by the gas stop
valve on the gas supply piping during the pressure tests,
as soon as the pressure exceeds 0.060 bar (60 mbar).
If pressure greater than 0.060 bar is applied to the gas
valve inlet the unit may be damaged. In this case it is
mandatory to add a pressure reducer.
Connect condensation pipe for modulating burner.
2 stages burner is not supposed produce condensate
and the small amount of condensate possibly produced
in particular working conditions will in case evaporate
Figure 9 - Typical Gas Supply pipework
KEY
1 Main burner gas solenoid valve
2 Pilot burner gas solenoid valve
3 Pressure stabiliser
4 Safety gas solenoid valve
5 Gas lter (small section)
6 Anti-vibration joint
7 Gas lter (large section)
8 Gas valve
Gas connection Ø : male UNI/ISO 228/1 G3/4” tightening torque
150Nm all range
Smoke outlet features
Unit is shipped with an outlet adaptor for connection to
exhaust pipe. If there is no exhaust pipe used, a terminal
feature located on the accessories should be installed.
Note: Exhaust pipe material has to be chosen carefully to
avoid corrosion.
Figure 10 - Exhaust gas terminal installation
PCH 132
PCH 162 - PCH 212
10m
Max 60 mbar
Pressure reducer