Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
IC140 IC150 IC170 IC190 IC220 IC250 IC270
Electrical Data (2) (3)
Main Power Supply
V/Ph/
Hz
400 / 3
/50
400 / 3 /50
400 / 3
/50
400 / 3 /50 400 / 3 /50
400 / 3
/50
400 / 3 /50
Unit Max Amps A 118 128 154 170 203 224 239
Unit Start Up Amps (without soft
starter)
A 250 296 331 384 417 484 578
Unit Start Up Amps (with soft
starter)
A 195 227 255 293 326 372 434
Maximum Short Circuit rating for
0,3 sec
kA 15 15 15 15 15 15 15
Disconnect swich
Disconnect swich (standard unit) Sirco 250A Sirco 250A Sirco 250A Sirco 315A Sirco 315A Sirco 400A Sirco 400A
Cross section max (standard unit) mm
2
150 150 150 240 240 240 240
Disconnect swich (unit with
electrical heater option)
Sirco 500A Sirco 500A Sirco 500A Sirco 630A Sirco 630A Sirco 630A Sirco 630A
Cross section max (unit with
electrical heater option)
mm
2
240 240 240 2x300 2x300 2x300 2x300
Disconnect swich (unit with other
options that electrical heater)
Sirco 400A Sirco 400A Sirco 400A Sirco 500A Sirco 500A Sirco 500A Sirco 500A
Cross section max (unit with
electrical heater option)
mm
2
240 240 240 240 240 240 240
Electric data with option (2) (3)
Electric Heater A 108 108 144 144 162 162 162
Indoor fan : Oversized A 11.1 11.1 9.0 14.8 0.0 0.0 0.0
Exhaust Fan A 9.4 9.4 9.4 9.4 9.4 9.4 9.4
Return Roofcurb A 13.2 13.2 13.2 22.0 22.0 22.0 22.0
Heat Recovery (not included current
for oversized fan)
A 12.9 12.9 12.9 12.9 12.9 12.9 12.9
Heat Recovery - High airow (not
included current for oversized fan)
A 21.9 21.9 21.9 21.9 21.9 21.9 21.9
Gas burner - modulation - 132 kW A 0.8 0.8 0.8 0.8 0.8 0.8 0.8
Gas burner - modulation - 162 kW A 1.1 1.1 1.1 1.1 1.1 1.1 1.1
Gas burner - modulation - 212 kW A 1.1 1.1 1.1 1.1 1.1 1.1 1.1
Frame
Frame # 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Compressor
Number of Circuits # 2 2 2
2 2 2 2
Number of Compressor per Circuits # 2 2 2
2 2 2 2
Type Scroll Scroll Scroll
Scroll Scroll Scroll Scroll
Model
DSH140-4/
DSH140-4
DSH161-4/
DSH161-4
DSH184-4/
DSH184-4
DSH184-4/
DSH240-4
DSH240-4/
DSH240-4
DSH240-4/
DSH295-4
DSH295-4/
DSH295-4
Max Amps per Compressor A
22,9 /
22,9
25,55 /
25,55
29,29 /
29,29
29,29 /
38,55
38,55 /
38,55
38,55 /
46,02
46,02 /
46,02
Locked Rotor Amps per Compressor A 147 / 147 158 / 158 197 / 197
197 / 215 215 / 215 215 / 260 260 / 260
Oil & Refrigerant (6)
Oil quantity per compressors CMP1
/ CMP2 (6)
l 3,3 / 3,3 3,3 / 3,3 3,6 / 3,6
3,6 / 6,7 6,7 / 6,7 6,7 / 6,7 6,7 / 6,7
Oil quantity ckt1/ckt2 (6) l 6,6 / 6,6 6,6 / 6,6 7,2 / 7,2
10,3 / 10,3 13,4 / 13,4 13,4 / 13,4 13,4 / 13,4
Internal Free Volume CMP1 / CMP2 l
14,3 /
14,3
14,3 / 14,3 14,6 / 14,6
14,6 / 31,0 14,6 / 31,0
31,0 /
31,0
31,0 / 31,0
Refrigerant load per circuit
(kg CKT1/ kg CKT2) R410A
kg 10,0/10,0 10,0/10,0 10,5/10,5
10,5/10,5 11,5/11,5 12,0/12,0 12,0/12,0
Refrigerant load per circuit
(kg CKT1/ kg CKT2) R454B
kg 8,5/8,5 8,5/8,5 9,0/9,0
9,0/9,0 10,0/10,0 10,5/10,5 10,5/10,5
Outdoor Coil
Type MCHE MCHE MCHE
MCHE MCHE MCHE MCHE
Face Area m
2
3.28 3.28 3.28
3.28 3.28 4.61 4.61
Fine per foot fpf 23 23 23
23 23 23 23
Number of Tubes in the height / MCHE passes 155 (127-28)