EasyManua.ls Logo

Trane BCVC - Unit Wiring Diagrams and Information; Supply Power Wiring; Electrical Connections; Electrical Grounding Restrictions

Trane BCVC
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
SS-APG010C-EN
Refrigerant Piping Examples
Figure 8. Indoor coil with two distributors (single-circuit TTA/TWA units)
1 Pitch the liquid line 1 inch per 10 feet (1 cm per
3 m) so that the liquid refrigerant drains toward
the indoor coil. Use the liquid-line size
recommended in Table 3, p. 16.
2 Provide one expansion valve (TXV)
per distributor.
TWA heat pumps only: Provide one check
valve for each expansion valve.
3 Pitch the gas line leaving the coil so that it
slopes away from the coil by 1 inch per 10 feet
(1 cm per 3 m).
4 Arrange the gas line so that suction gas leaving
the coil flows downward, past the lowest gas-
header outlet, before turning upward. Use a
double-elbow configuration on all lower branch
circuits to isolate the TXV bulb from suction-
header conditions. See “Gas Line: Routing,p. 7.
5 For all coil branch circuits in the gas line, use a
tube diameter that is one size smaller than the
gas-line size recommended in Table 3, p. 16.
6 For vertical risers, use the tube diameter
recommended in Table 3, p. 16. Ensure that the
top of the riser is at least 1 foot (30 cm) above
the lowest point.
7 Pitch the gas line by 1 inch per 10 feet (1 cm per
3 m) toward the indoor coil.
8 Insulate the gas line.

Other manuals for Trane BCVC

Related product manuals