Table 11. Evaporator and condenser bundle weights
Model Shell Size
Bundle
Size
(a)
Evaporator
Condenser
Shell
(b)
Waterbox
(c)
Shell
(d)
Waterbox
(c)
lb
kg
lb
kg
lb
kg
lb
kg
CVHE
032S 320 2778 1260 653 296 2458 1115 644 292
032L 320 3483 1579 653 296 3006 1363 644 292
CVHE
CVHF
CVHG
050S 700 4897 2221 1061 481
3526
(e)
1599 1328 602
050L 700 5984 2714 1061 481
4436
(e)
2012 1328 602
080S 1400 7884 3283 2490 1129 5280 2394 2565 1164
080L 1400 9653 4066 2490 1129 6776 3073 2565 1164
142M 1420 11036 5005 3701 1679
N/A N/A
5330 2418
142L 1420 11938 5414 3701 1679 10995 4987 5330 2418
142E 1420 12921 5860 3701 1679
N/A N/A
5330 2418
210L 2100 14755 6692 6403 2904 14154 6420 7319 3320
250 2500 20068 9102 8343 3784 17200 7801 9144 4148
CDHF
CDHG
210D 2100 22437 10177
8382
(f)
3802
(f)
22635 10267
8928
(f)
4050
(f)
250D 2500 24610 11162
10954
(f)
4969
(f)
25853 11726
11442
(g)
5190
(f)
250M 2500 28679 13008
10954
(f)
4969
(f)
29817 13524
11442
(f)
5190
(f)
250X 2500 31902 14470
10954
(f)
4969
(f)
33486 15188
11442
(f)
5190
(f)
Note: All weights are nominal and ±10%.
(a)
Bundle weights are for the maximum bundle size for chiller family with TECU.035 tubes.
(b)
Evaporator shell weight includes: Evaporator + Control Panel + Legs; waterbox weight is NOT included.
(c)
Based on two-pass marine, 300 lb (136 kg); includes supply and return.
(d)
Condenser shell weight includes: Condenser + Oil Tank + Purge + Legs; waterbox weight is NOT included.
(e)
Condenser bundle is a 500.
(f)
Based on 1-pass marine, 300 lb (136 kg); includes supply and return.
Table 12. Unit-mounted starters/Adaptive Frequency™™ drives
lb
kg
Low Voltage (less than 600 volts)
Wye Delta
557 252
Solid State 557 252
Adaptive Frequency Drive (less than 600 volts)
405 amp
1680 762
608 amp
1680 762
900 amp
3000 1360
1210 amp
3000 1360
Medium Voltage (2300–6600 volts)
Across the line 557 252
Primary Reactor
1586 719
Autotransformer 1639 743
Note: All weights are nominal and ±10%.