CG-PRC002A-EN
11
Performance
Adjustment Factors
Fig. 06 - Ethylene and Propylene Freezing Points
Fig. 05 - Propylene Glycol Performance Factors
% of Antifreezing in Weight
% of Ethylene Glycol in Weight
% de Propylene Glycol in Weight
Tab. 02 - Altitude Correction Factors
Altitude Capacity Consumption Water Flow
0
1,000
1,000
1,000
500
0,997
1,012
0,997
1000
0,994
1,024
0,994
1500
0,991
1,037
0,991
2000
0,987
1,052
0,987
2500
0,983
1,067
0,983
3000
0,978
1,084
0,978
Ethylene Glycol
Propylene Glycol
Temperature°C
Temperature °F
Flow GPM
Capacity
Compressor Power
Adjustment Factor
Flow GPM
Capacity
Compressor Power
Adjustment Factor
Fig. 04 - Ethylene Glycol Performance Factors