22
6.16 Maintenance Plan for Air Handling Units
The following table (see Table 4) gives recommended maintenance intervals for the CLCH unit. Intervals are based upon normal
running conditions, in a moderate climate, and assuming 24-hour running.
Units operating outside these guidelines may require shorter or longer maintenance intervals.
Table 4 – Recommended Maintenance Intervals
Component Check the Following Weekly Monthly 3-6 Monthly Annually
(see section) (see section) (see section) (see section)
Fan / Motor Fan In General Yes (6.1)
For Corrosion Yes (6.1)
Flexible Connection Yes (6.1)
Anti-Vibration Mounts Yes (6.1)
Inlet Guide Vane Controller Yes
Drainage Yes (6.1)
Fan Bearing Yes (6.2)
Motors In General Yes (6.3)
Motor Bearing Yes (6.3)
Belt Drive In General Yes (6.5)
Filters Panel Or Bag Filters Yes (6.7)
Roll Filters Yes
Absolute Filters Yes
Coils Fin Block Yes (6.8.1.)
Frost Protection Yes (6.8.2.)
Drainage Yes
Drop Eliminator Yes (6.8.3.)
Steam Coils Yes (6.8.4.)
Humidifiers Scaling Yes (6.10)
Condensate Drain Yes (6.10)
Dampers Dampers Yes (6.11)
Attenuators Scilencers Yes (6.12)
Inlet / Outlet Hoods And Louvers Yes (6.13)
Energy Recovery Components Plate Heat Exchangers Yes (6.14)
Thermal Wheel Yes (6.15)
Controls Control Box And Wiring Yes
6. Maintenance