LED
Color
EEV
Fault LED
Description
3 Flash
Suction Pressure Transducer input is out of range
(Replace transducer) (1)
4 Flash
Suction Temperature Sensor input is out of range
(Replace sensor) (1)
5 Flash
Coil has short circuit
(Replace Coil) (2)
6 Flash
Valve is not responding to a position change command
(Possible stuck valve)
7 Flash
Valve is responding but system is not performing properly
(Low charge or restriction)
8 Flash
Compressor is not pumping
(3)
9 Flash
Low superheat in Cooling Mode
(Indoor TXV stuck open or ID Fan failure)
10 Flash
Not used at this time
(3) Monitor superheat and pressure: <3' SH for 5 minutes with valve @ minimum position, Monitor off-cycle
pressure and compare to next on-cycle for pressure drop within 60 seconds
Red
(1) Valve will close and LPCO will trip
OFF
1 Flash
Standby
Coil has an open circuit or intermittent short
(Replace Coil)
(2) Power supply will shut down to protect board
EEV Fault Codes
EEV not used on all models
2 Flash
Control has detected an internal failure
(Replace EEV control board)
The following may require additional diagnostics
Notes: