4TWZ0060A1000A
SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
LOWER
Dip Switch 1- ON
MIDDLE
Dip Switch 2-ON
Dip Switch 3-ON
UPPER
Max Lift
25
20
15
10
0
10 20 25 30 40 60 80
Dip Switch 3-ON
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
Max Lift
25
20
15
10
0
10 20 25 30 40 60 80
4TEE3_10 Downflow & Horizontal Left Only
All other approved, matched systems.
CHARGING METHOD
This model has ComfortLink™ II and Charge Assist™
features. Charge Assist™ can be used in cooling mode
only.
For complete instructions on using Charge Assist,™
please see page 4.
2
SCHEMATIC DIAGRAM
MANUAL CHARGING BELOW 55°F OD AMBIENT –
IN HEATING MODE (HP MODELS ONLY)
1. The only recommended method of charging at outdoor
ambients below 55°F, is to weigh in the charge in the heat-
ing mode.
2. Check liquid line temperature and pressure (at the OD
valves) to obtain a minimum of 10°F subcooling.
3. It is important to return in the spring or summer to accu-
rately charge the system in the cooling mode at outdoor
ambients from 55°F-120°F.